West Virginia Bids > Bid Detail

FCC Hazelton - Water Heating System - PRODUCT ONLY

Agency:
Level of Government: Federal
Category:
  • 45 - Plumbing, Heating, and Sanitation Equipment
Opps ID: NBD00159132529148595
Posted Date: Nov 16, 2023
Due Date: Nov 27, 2023
Source: https://sam.gov/opp/5ef14ca99f...
Follow
FCC Hazelton - Water Heating System - PRODUCT ONLY
Active
Contract Opportunity
Notice ID
15B12124Q00000002
Related Notice
Department/Ind. Agency
JUSTICE, DEPARTMENT OF
Sub-tier
FEDERAL PRISON SYSTEM / BUREAU OF PRISONS
Office
USP HAZELTON
Looking for contract opportunity help?

APEX Accelerators are an official government contracting resource for small businesses. Find your local APEX Accelerator (opens in new window) for free government expertise related to contract opportunities.

APEX Accelerators are funded in part through a cooperative agreement with the Department of Defense.

The APEX Accelerators program was formerly known as the Procurement Technical Assistance Program (opens in new window) (PTAP).

General Information
  • Contract Opportunity Type: Combined Synopsis/Solicitation (Original)
  • All Dates/Times are: (UTC-05:00) EASTERN STANDARD TIME, NEW YORK, USA
  • Original Published Date: Nov 16, 2023 02:17 pm EST
  • Original Date Offers Due: Nov 27, 2023 02:00 pm EST
  • Inactive Policy: 15 days after date offers due
  • Original Inactive Date: Dec 12, 2023
  • Initiative:
    • None
Classification
  • Original Set Aside:
  • Product Service Code: 4520 - SPACE AND WATER HEATING EQUIPMENT
  • NAICS Code:
    • 238220 - Plumbing, Heating, and Air-Conditioning Contractors
  • Place of Performance:
    Bruceton Mills , WV 26525
    USA
Description

FCC Hazelton requires a quantity of 4 each indirect plate and frame water heater plus 4 each pumps to accompany the water heaters. Vendors are required to have active SAM.Gov registration and to provide their UEI. A signed SF1449 must be submitted to be considered received. This requirement is for product ONLY. All quotes and bids are required to be submitted to Kelly Brown, Supervisory Contract Specialist with FCC Hazelton at k1roberts@bop.gov (Note: that is a number one after the K) AND HAX-ProcurementProp-S@bop.gov. Quotes must be valid for at least 30 days after close of bids on November 27, 2023 at 2 PM EDT. Specific product requirements below and example spec sheets attached.



Indirect Plate And Frame Water Heater: (4)



Dimensions cannot Exceed: 63” Height Max; 22” Width max; 61” Base Length – MUST FIT THROUGH STANDARD 36” door. Product should not exceed 1200 lbs – Lite Weight Preferred



FEATURES:



ASME DOUBLE WALL HEAT EXCHANGER



• 316L Stainless Steel



• 150 psi Working Pressure



DIGITAL DISPLAY



• DHW Set Point Range 90°F to 180°F



ADVANCED TEMPERATURE CONTROL



MODULATING CONTROL VALVE



SCALE REDUCING PUMP



AUTOMATIC AIR VENT



ASME TEMPERATURE & PRESSURE RELIEF VALVE



• 210°F and 150 psi



ADJUSTABLE HIGH LIMIT



WYE STRAINERS - DOMESTIC PIPING AND



BOILER PIPING



ISOLATION VALVES - DOMESTIC PIPING AND BOILER PIPING



MODBUS COMMUNICATION



WARRANTY



• 5-Year limited warranty/1-Year limited parts



• Warranty for product only without services requirement



SUGGESTED SPECIFICATION



The Indirect Plate and Frame shall be constructed of a 316 stainless steel plate with EPDM gaskets. Maximum unit dimensions shall be: Length ___61_inches, Width ___22___inches and Height __63______ inches.



The Indirect Plate and Frame shall be a double wall. The plate and frame shall be constructed in accordance with the ASME Boiler and Pressure Vessel Code requirements, stamped and registered with the National Board of Boiler and Pressure Vessel Inspectors



The Indirect Plate and Frame shall have a 150 psi working pressure and be supplied with an ASME temperature and pressure relief valve. Standard equipment shall include Wye Strainers, Isolation Valves, Automatic Air Vent, Scale Reduction Pump, Adjustable High Limit and drain valve



The temperature control shall provide + or – 4 degrees Fahrenheit accuracy with up to a 50% change in load. Setpoint range between 90 and 180 F. Modbus communication shall be standard equipment. The modulating valve shall have a 1000 to 1 turndown. The Indirect Plate and Frame shall be suitable for use with polypropylene glycol, up to 50% concentration. The de-rate associated with the glycol will vary per glycol manufacturer.



Pump: (4) Specifications must meet all below requirements for pump withsystem control and monitoring key



Conditions of Service



Flow: 130 US GPM



Head: 32 ft



Efficiency: 68.6 %



Liquid: Water



Temperature: 60 °C



NPSH required: ft



Pump Data



Specific Gravity: 0.985



Maximum operating pressure: 12 bar



Liquid temperature range: -10 .. 110 °C



Maximum ambient temperature: 40 °C



Flange standard: GF



Pipe connection: GF65



Product number: On request



Motor Data



P1 max: 29 .. 1385 W



Mains frequency: 60 Hz



Enclosure class: X4D



Insulation class: F



ADDITIONAL INFORMATION: Domestic inlet temp Set point. DHW set point 90 to 180 degrees. GPH for all units together or for each if separated. GPH is for each unit. Each system will supply at minimum hot water to 64-cells, 10-showers, 2-mop closet and 1-staff restroom. Boiler water entering temp 160-180 degrees. Boiler water Leaving temp 120-140 degrees BTU I am looking for specifics on this. -These units are in use 24/7-365 if that helps.



For singled cell showers, 10 to be used at a time with a maximum of up to 128.


Attachments/Links
Contact Information
Contracting Office Address
  • 1460 SKY VIEW DRIVE PO BOX 450
  • BRUCETON MILLS , WV 26525
  • USA
Primary Point of Contact
Secondary Point of Contact
History
  • Nov 16, 2023 02:17 pm ESTCombined Synopsis/Solicitation (Original)

TRY FOR FREE

Not a USAOPPS Member Yet?

Get unlimited access to thousands of active local, state and federal government bids and awards in All 50 States.

Start Free Trial Today >